Split Casing Pump Refurbishment
After just two years of service, a pump inspection revealed heavy corrosion. Protecting these expensive pump housings from bi-metallic corrosion is crucial to extend their lifespan and avoid costly replacements.
Addressing severe corrosion in expensive pump housings
A pump inspection conducted after only two years of service uncovered severe corrosion attacks. These large pump housings are quite costly, making it essential to protect them against bi-metallic corrosion to prevent premature wear and expensive replacements.
Effective corrosion protection and maintenance for
pump housings
To address the bi-metallic corrosion in the pump housing, a thorough surface preparation was performed, including blasting and degreasing. Wencon Rapid was applied to fill dents and imperfections, followed by a two-layer Wencon Coating system to ensure optimal protection.
This approach restored the pump housing to its original shape and provided a durable barrier against further corrosion. The pump was then assembled, pressure tested, and prepared for delivery, ensuring long-term reliability and performance.